CLEAN ROOM MONITORING – REGULATORY STANDARDS         Ø  Air Classification as per Schedule  M              Grade      Maximum permitted number of particles   / m3 equal or above         at rest      in operation         0.5µm      5.0µm      0.5µm      5.0µm         A      3,520      29      3,500      29         B      35,200      293      3,52,000      2,930         C      3,52,000      2,930      35,20,000      29,300         D      35,20,000      29,300      not   defined      not   defined         Note:-       Grade A and B correspond to with class  100, M 3.5, ISO 5    Grade C correspond to with class 10000, M 5.5, ISO 7   Grade D correspond to with class 100000, M 6.5, ISO 8        Ø   Air Classifications by US FDA guideline on Sterile Drug  Products            Clean Area Classification      <0.5 µm Particles/ft3      <0.5 µm Particles/mt3      Microbiological Limit         cfu/ft3      cfu/m3         100      100      3,500      <1      ...